CONDENSATOR DOMINIT
SOFIA Voltage Regulated Harmonic Filter
SOFIA innovates in the automatic filtration of harmonics. SOFIA Anti-harmonic filter actively manages the reduction of harmonics by the THDU, unlike a classic Active filter, SOFIA cleans a network rather than a load. The control is carried out in an innovative way in Voltage, the installation of Current transformers is no longer necessary. Designed to operate at harmonic levels of 61000-2-4 Class 3 Industrial applications. Any type of industry. Chemicals, cement, automotive, metallurgy etc...
Rated voltage 400V 50Hz, three-phase Current / Frequency 360A / 250Hz Current without harmonic load 134…158A Capacitor sizing >900V Full load losses <2070W No-load losses <400W Ambient temperature -5/+40°C, average over 24 hours? 35°C Protection IP42 Dimensions (LxWxH) 800x600x2060mm Weight 575kg Cable entry From below Connections L1, L2, L3 and PE Fuse protection (on site) 3x500A gG Cable section 2 II 3x120/70mm² (Cu)